Skip to main content

Utilities

These are the essential utilities required for the biodryer to function.

dryer

Utilities Requirement​

CalloutUtilityRequirements
1Pneumatic Air1/2" NPT Between 1000 and 115 PSI
Max instant flow 3.28 cfm @ 115 PSI
2Condensates Discharge1" NPT Max instant flow 2 gpm
3Potable Water1/2" NPT Between 35 and 150 PSI
Max instant flow 20 gpm
4Hot Process Water Loop1' 1/2" Flange ASME B16.5, Class 150
40 gpm @ 70 PSI and 205°F
NAElectricity3ph, 480 V, 60 Hz 125 A breaker
Max contemporaneous load 45 A